电力系统自动化Issue(15):96-102,7.DOI:10.7500/AEPS20140806004
基于电压偏差向量2-范数的主动配电网故障定位新方法
Fault Location Method of Active Distribution Networks Based on 2-norm of Voltage Deviation Vectors
摘要
Abstract
With the increasing interconnection of distributed generators in distribution networks,some of the existing fault location algorithms may fail.A fault location method based on the minimum 2-norm of voltage deviation vectors is proposed. Firstly,the fault current is injected into each bus of the distribution network model to calculate the voltage variation of the power source.Secondly,the difference between measured voltage variation and calculated voltage variation is analyzed,and the fault current injected bus corresponding to the minimum difference is searched and determined as the first bus of the fault section.Finally,the other bus of the fault section is determined according to the variation trend.An IEEE 34-bus system is chosen to verify the algorithm,the results showing that the algorithm has clear physical meaning,simple calculation process and good fault location accuracy.The more distributed generation is connected,the better fault location accuracy will be.关键词
故障区段定位/配电网/分布式发电/2-范数Key words
fault section location/distribution network/distributed generation/2-norm引用本文复制引用
戴志辉,崇志强,李川,李芷筠..基于电压偏差向量2-范数的主动配电网故障定位新方法[J].电力系统自动化,2015,(15):96-102,7.基金项目
国家自然科学基金资助项目(51307059) (51307059)
河北省自然科学基金资助项目(E2014502065) (E2014502065)
中央高校基本科研业务费专项资金资助项目(2014MS86) (2014MS86)
国家重点基础研究发展计划(973计划)资助项目(2012CB215200)。This work is supported by National Natural Science Foundation of China (No.51307059),Hebei Provincial Natural Science Foundation of China (No. E2014502065), Fundamental Research Funds for the Central Universities (No.2014MS86),and National Basic Research Program of China(973 Program)(No.2012CB215200) (973计划)