摘要
Abstract
Based on the effectiveness and directionality of generator reactive power reserve(GRPR),an optimization model for minimizing effective GRPR considering static shunt reactive power compensation is proposed.Using the theory of Benders decomposition algorithm,the original problem is decomposed into a master problem that corresponds to normal operation condition and several sub-problems that correspond to anticipated contingency and stressed operation conditions.In order to reduce the scale of model solving,a screening algorithm for sub-problems is designed,which is capable of improving the overall model solving efficiency of Benders algorithm. In the end, case studies on an IEEE 39-bus system have verified the effectiveness of the proposed algorithm.关键词
发电机无功储备/无功补偿/协调优化/静态电压稳定/Benders 分解Key words
generator reactive power reserve (GRPR)/reactive power compensation/coordinated optimization/static voltage stability/Benders decomposition引用本文复制引用
邱一苇,吴浩,宋永华,孙维真..考虑静态并联无功补偿的发电机无功储备优化方法[J].电力系统自动化,2015,(18):31-36,48,7.基金项目
国家电网公司科技项目“省级电网运行控制协调优化技术研究与示范” ()