摘要
Abstract
There is no experience in design and construction of±800 kV and±500 kV double-circuit DC transmission lines on the same tower, which improves utilization rate of the power transmission corridor effectively. For electromagnetic environmental problem, the total electric field, ion current density, radio interference and audible noise under different types of towers and conductor arrangements are calculated based on Deutsch assumption and empirical formulas. The results show that the required line-to-ground height is smaller while±500 kV line are arranged on the lower arm, the required width of corridor is narrower but the audible noise is higher when the same polarity are arranged on different side. The electromagnetic environment is also analyzed under different conductor types, conductor distances and height to ground, and the results provide reference for project design.关键词
电磁环境/合成场强/无线电干扰/可听噪声/同塔双回直流输电线路Key words
electromagnetic environment/total electric field/radio interference/audible noise/double-circuit DC transmission lines on the same tower分类
信息技术与安全科学引用本文复制引用
吴高波,李健,陈媛,罗楚军,汪如松,林芳..±800kV与±500kV同塔双回直流输电线路电磁环境研究[J].电网技术,2015,39(9):2532-2538,7.