On the basis of analysis on some questions of relay protection in auxiliary power systems,like the imperfection in configuration and the actuation time is too long,a scheme was proposed for relay protection design,such as configuring a specialized main protection for 6 kV busbar,adding a time limited current fast-trip protection on the high-voltage side of low-voltage transformers in auxiliary power system,optimizing the cooperation of reserve protections and then designing the configuration of relay protection in auxiliary power system according to the optimizing rule.Taking a 600 MW unit as the example,settings calculation was carried out.The results proved that the configuration of relay protection in auxiliary power system is integrated perfectly due to the optimization,the coverage of protection is reasonable and the actuation time of reserve protection has been remarkably shortened.Thus,the actuation speed and security of the auxiliary power system are promoted.关键词
厂用电系统/继电保护/配置/专用主保护/后备保护/动作时间/整定计算Key words
auxiliary power system/relay protection/configuration/specialized main protection/reserve pro-tection/actuation time/settings calculation分类
信息技术与安全科学