| 注册
首页|期刊导航|机电工程技术|变电站二次电缆屏蔽线腐蚀断裂的分析

变电站二次电缆屏蔽线腐蚀断裂的分析

曾庆汇 刘娟

机电工程技术Issue(5):55-58,91,5.
机电工程技术Issue(5):55-58,91,5.DOI:10.3969/j.issn.1009-9492.2013.05.015

变电站二次电缆屏蔽线腐蚀断裂的分析

Analysis of Secondary Shield Cable Corroding and Cracking in Substations

曾庆汇 1刘娟2

作者信息

  • 1. 南昌供电公司,江西南昌 330006
  • 2. 湖南省电力培训中心,湖南长沙 410000
  • 折叠

摘要

Abstract

  This paper recommends the importance of secondary cable shielding grounding scheme in substations. The appearance of the shield grounding corrosion has been investigated from the substation environment ,secondary cable shielding wire corrosion condition, the corrosion point distribution and the shield current. While the map about corrosion product sample is analyzed respectively from the composition,physical and chemical characteristics,crystal structure and corrosion fracture morphology. According to the shielded wire corrosion reasons,the cause of the corrosion process is concluded which is about the copper clad aluminum shielded wire. This paper lists the simple identification methods of the copper clad aluminum shielded wire,and puts forward some solutions and suggestions about that.

关键词

二次电缆/屏蔽层/腐蚀/断裂/鉴定

Key words

secondary cable/shielding scheme/corrosion/crack/identify

分类

信息技术与安全科学

引用本文复制引用

曾庆汇,刘娟..变电站二次电缆屏蔽线腐蚀断裂的分析[J].机电工程技术,2013,(5):55-58,91,5.

机电工程技术

1009-9492

访问量0
|
下载量0
段落导航相关论文