Abstract

Make a 5% error filed test for a unit of protective current transformer in a wind farm. The test data included the load impedance and the accuracy limit coefficient, etc. Based on three different checking criteria in DL/T 886-2004 The guide for selection and calculation of current transtormers and voltage transtormers, including general choice checking, rated limiting secondary e.m.f. checking, and the accuracy limit coefficient checking, with which calculating the secondary measurement value as short-circuit fault occured on the main transformer high voltage side. The measurement result showed that the current transformer met the requirement of 5% error, which could guarantee the secondary current value correct and effective, and avoid the maloperation and refuse operation resulted from the overlarge current value.

关键词

风电场/电流互感器/5%误差曲线/准确限制系数/二次电动势/性能估算

Key words

wind farm/current transformer/5% error curve/accuracy limit factor/secondary e.m.f/performance evaluation