Unit 2 in some power plant was forced to shutdown, because the air source of slight pressure device was too moist, the water removal capacity of air compressors was decling, environmental temperature was quite different, the enclosed busbar had leakage, some faults existed in parts of busbar′s structure of branch circuit TA, which caused the dewing and hydrops in isolated phase busbar in TA section, and further caused the discharge and shutdown. The measures of replacing the air source of air compressor, equipped with gas heating device, and transforming the isolated phase busbar TA section of HV auxiliary transformer high voltage side, eliminated the dewing and hydrops, which ensured the safe and stable operation of the unit.关键词
离相封闭母线/电流互感器/结露/积水/微正压装置Key words
isolated phase busbar/ammeter transformator/dewing/hydrops/slight pressure device分类
信息技术与安全科学引用本文复制引用
李建国,卢福平,郝婧敏..离相封闭母线电流互感器段积水原因分析及处理[J].内蒙古电力技术,2015,(5):95-97,3.