首页|期刊导航|宁夏电力|发电机定子冷却水水质超标事故分析

发电机定子冷却水水质超标事故分析OA

Accident analysis on cooling water quality over standard of generator stator

中文摘要英文摘要

  针对六盘山热电厂1号机组发电机定子冷却水水质超标事件,进行原因分析,制定相应的防范及整改措施。分析结果表明:造成此次定子冷却水水质超标事件的主要原因为城市中水水质超标,导致水处理系统酸碱使用量增加,碱液储量不足,除盐系统失效,最终使定子冷却水水质无法控制,造成超标。

Aiming at the problems of cooling water quality over standard of generator stator in unit 1 of Liupanshan Thermal Power Plant, analyzes the case of fault and reasones out a solution to the prob-lem. The analysis result shows that the water quality of urban treated water is over standard, bringing on acid and alkali dosage increase in water treatment system, because of the reserves of alkali liquid is less, resulting in the desalting system invalidation, fina…查看全部>>

冯冰;卢建新;许多喜

宁夏银仪电力设备检修安装有限公司,宁夏 银川 750001宁夏银仪电力设备检修安装有限公司,宁夏 银川 750001宁夏银仪电力设备检修安装有限公司,宁夏 银川 750001

信息技术与安全科学

发电机定子冷却水水质超标

generatorcooling water of statorwater quality over standard

《宁夏电力》 2013 (3)

68-71,4

10.3969/j.issn.1672-3643.2013.03.018

评论

您当前未登录!去登录点击加载更多...