一起厂用变压器差动保护误动引起的停机故障分析与改进措施
Analysis and Improvencent of a Shutdown Event Caused by the Differential Protection Malfunction of the Auxiliary Transformer
丁明利 1屠士风2
作者信息
- 1. 温州市工业投资集团有限公司,浙江 温州 325000
- 2. 浙江浙能乐清发电有限责任公司,浙江 乐清 325609
- 折叠
摘要
Abstract
The malfunction of boiler differential protection device causes MFT in power plant #2 unit. By cause analysis and preventive measures adopted against the trip event, the importance of matching between I&C software configuration and electrical control circuit design of local devices is discussed. To improve the reliability of thermal control system, reliability of both hardware of control system and software configuration should be improved to prevent protection malfunction or refuse operation due to unreasonable software config-uration and a chain of abnormal interlocking actions of other equipment because of a single equipment failure to prevent the event from expansion.关键词
保护/误动/热控系统Key words
protection/malfunction/thermal control system分类