制冷技术Issue(2):14-16,3.DOI:10.3969/j.issn.2095-4468.2013.02.104
重力式热管空调机组运行特性试验研究
Experimental Investigation of Operating Characteristic of Two-phase Closed Thermosyphon Type Air Conditioning Unit
王爱辉 1罗高乔 1汪韩送1
作者信息
- 1. 中国电子科技集团公司第十六研究所,合肥 230043
- 折叠
摘要
Abstract
A two-phase closed thermosyphon type air conditioning unit was designed, and the operating characteristic was tested. The results showed that, when the temperature difference between the indoor and outdoor is 10℃ and air volume is 3500 m3/h, the cooling capacity can reach up to 4000 W. Under the certain temperature difference between the indoor and outdoor, the influence of increasing air volume on the cooling capacity decreases slowly. Under the certain air volume, the cooling capacity increases with the increase of the temperature difference between the indoor and outdoor. Under the same condition, when the number of heat pipe doubles, the cooling capacity increases by 14%, but the cost of the unit increases by above 30%, and the economy gets worse.关键词
重力式热管/风量/温差/温度效率Key words
Two-phase closed thermosyphon/Air volume/Temperature difference/Temperature efficiency引用本文复制引用
王爱辉,罗高乔,汪韩送..重力式热管空调机组运行特性试验研究[J].制冷技术,2013,(2):14-16,3.