Abstract

  A two-phase closed thermosyphon type air conditioning unit was designed, and the operating characteristic was tested. The results showed that, when the temperature difference between the indoor and outdoor is 10℃ and air volume is 3500 m3/h, the cooling capacity can reach up to 4000 W. Under the certain temperature difference between the indoor and outdoor, the influence of increasing air volume on the cooling capacity decreases slowly. Under the certain air volume, the cooling capacity increases with the increase of the temperature difference between the indoor and outdoor. Under the same condition, when the number of heat pipe doubles, the cooling capacity increases by 14%, but the cost of the unit increases by above 30%, and the economy gets worse.

关键词

重力式热管/风量/温差/温度效率

Key words

Two-phase closed thermosyphon/Air volume/Temperature difference/Temperature efficiency