制冷学报Issue(1):81-83,93,4.DOI:10.3969/j.issn.0253-4339.2013.01.081
辐射吊顶换热性能的实验研究
Experimental Study on Radiant Ceiling’s Heat Transfer Performance
摘要
Abstract
The heating and cooling capacity of two different radiant ceilings are tested. Testing results show that the cooling performance of the radiant ceiling with parallel capillary coil is better than the series-connected coil type, when the temperature difference between the room and the average temperature of the supply and return water is 8℃, the cooling capacity of the capillary type radiant ceiling is 64.4W/m2, and the coil type is 55.0 W/m2. For the same radiant ceiling in the same temperature difference between the room and the average temperature of the supply and return water, the difference between cooling and heating capacity is no more than 10%. In addition, the radiant ceiling with parallel capillary tubes has less flow resistance than the series-connected coil ceiling.关键词
换热性能/辐射吊顶/实验研究Key words
heat transfer performance/radiant ceiling/experimental investigation分类
通用工业技术引用本文复制引用
于国清,陶勤练..辐射吊顶换热性能的实验研究[J].制冷学报,2013,(1):81-83,93,4.基金项目
国家自然科学基金(50976073)资助项目.(The project was supported by the National Natural Science Foundation of China (No.50976073).)本文受上海市教委重点学科建设项目(J50502)资助.(The project was supported by the Shanghai Leading Academic Discipline Project(No.J50502).) (50976073)