10 kV配电网中中性点接地电阻柜保护误动原因分析与解决措施

王亮

内蒙古电力技术2015,Vol.33Issue(6):79-81,85,4.
内蒙古电力技术2015,Vol.33Issue(6):79-81,85,4.DOI:10.3969/j.issn.1008-6218.2015.06.015

10 kV配电网中中性点接地电阻柜保护误动原因分析与解决措施

False Protection Analysis of Neutral Point Grounding Resistance Cabinet in 10 kV Distribution Network and Its Treatment

王亮1

作者信息

  • 1. 鄂尔多斯电业局,内蒙古 卾尔多斯 017010
  • 折叠

摘要

Abstract

The application of neutral point grounding resistance cabinet can realize the zero sequence current protection configuration of 10 kV distribution network and fault trip, but due to the application of immature technology, it could easily lead to protection malfunction accident. Through the analysis of the multiple protection malfunction occurred during the operation of the 110 kV substation neutral grounding resistor cabinet within Ordos grid, the main causes are the error of the zero sequence TA measurement, the error of the cable shield to the ground wire and the error of the 10 kV feeder switch protection malfunction, etc., and formulate the corresponding solution measures, so as to achieve the effective application and management of neutral point grounding resistance cabinet in 10 kV distribution network.

关键词

10kV配电网/中性点接地电阻柜/零序电流保护/零序TA/10kV馈线开关/电缆屏蔽层接地线

Key words

10 kV distribution network/neutral point grounding resistance cabinet/zero sequence current protection/zero sequence TA/10 kV feeder switch/cable shield ground wire