| 注册
首页|期刊导航|内蒙古电力技术|变电站避雷器故障原因分析及解决措施

变电站避雷器故障原因分析及解决措施

叶涛

内蒙古电力技术2015,Vol.33Issue(6):93-96,100,5.
内蒙古电力技术2015,Vol.33Issue(6):93-96,100,5.DOI:10.3969/j.issn.1008-6218.2015.06.024

变电站避雷器故障原因分析及解决措施

Cause Analysis and Solving Measures on Breakage Failure of Arrester in Substation

叶涛1

作者信息

  • 1. 内蒙古电力(集团)有限责任公司,呼和浩特 010020
  • 折叠

摘要

Abstract

The V phase 220 kV surge arrestor exploded in a substation in Ulanqab. Through the disintegration of inspection, electrical testing and theoretical analysis for the failure surge arrester and the same batch of products, the cause of the failure is due to the bad material and technology of heat shrink tube used by surge arrester remain volatile matter, lead to the external insulation strength of core decreased, eventually, developed into a whole breakover or breakdown through the surge arrester. The author put forward measures and suggestion to strengthen equipment selection and improve the application rules of infrared diagnosis.

关键词

避雷器/热缩管/氧化锌阀片/工频电压耐受时间

Key words

surge arrester/heat shrink tube/zinc oxide resistor/power-frequency voltage tolerance time

分类

动力与电气工程

引用本文复制引用

叶涛..变电站避雷器故障原因分析及解决措施[J].内蒙古电力技术,2015,33(6):93-96,100,5.

内蒙古电力技术

1008-6218

访问量0
|
下载量0
段落导航相关论文