中国电机工程学报2015,Vol.35Issue(24):6566-6572,后插34,8.DOI:10.13334/j.0258-8013.pcsee.2015.24.034
交流电晕笼无线电干扰试验校准系数研究
Research on Measurement Calibration Coefficient of Radio Interference With AC Corona Cages
裴春明 1陈豫朝 1陈小月 2蓝磊 2肖国洲 2文习山2
作者信息
- 1. 中国电力科学研究院,湖北省武汉市 430074
- 2. 武汉大学电气工程学院,湖北省武汉市 430072
- 折叠
摘要
Abstract
The excitation function measured from radio interference test corona cages should be calibrated before being applied to radio interference calculation of the transmission line. The calibration factor is usually obtained by calibration experiments. However, the accuracy of calibration experiments is affected by the test condition and environment. This paper analyzed the theoretical calibration factor based on the circuit analysis method, which is more economic and convenient than calibration experiments. The distributed parameter model of the corona cage test circuit was established, and according to the independence of the corona discharge pulse in space and time, curves of the calibration coefficient for the corona discharge source at different position were obtained. Thus, the calibration coefficient was calculated, which was compared with the one obtained from proportion of capacitance. The results showe that the theoretical analysis method presented can be applied to calibrate the excitation function from corona cage tests, and it is economical and practical.关键词
电晕笼/无线电干扰/电晕电流/激发函数/校准系数Key words
corona cage/radio interference/corona current/excitation function/calibration coefficient分类
信息技术与安全科学引用本文复制引用
裴春明,陈豫朝,陈小月,蓝磊,肖国洲,文习山..交流电晕笼无线电干扰试验校准系数研究[J].中国电机工程学报,2015,35(24):6566-6572,后插34,8.