| 注册
首页|期刊导航|电力系统自动化|多频振荡下失步解列判据的适用性分析

多频振荡下失步解列判据的适用性分析

夏成军 陈翠琼 涂亮 陈亦平 门锟

电力系统自动化Issue(4):26-31,6.
电力系统自动化Issue(4):26-31,6.DOI:10.7500/AEPS20150525008

多频振荡下失步解列判据的适用性分析

Applicability Analysis of Out-of-step Splitting Criteria Under Multi-frequency Oscillation

夏成军 1陈翠琼 1涂亮 2陈亦平 3门锟2

作者信息

  • 1. 华南理工大学电力学院,广东省广州市 510640
  • 2. 南方电网科学研究院有限责任公司,广东省广州市 510080
  • 3. 中国南方电网电力调度控制中心,广东省广州市 510623
  • 折叠

摘要

Abstract

The criteria for out-of-step separation equipment in current domestic engineering fields are acquired from the out-of-step two-machine equivalent power system. Its applicability under multi-frequency oscillation is yet to be found out. Expressions of electrical quantities are inferred based on a three-machine equivalent system.And it is found that the out-of-step center would migrate between different transmission lines and different positions even on one and the same transmission line.In addition,the more distinct the different modulations are,the more transmission lines will there be for the out-of-step center to migrate in between.Besides,the three out-of-step splitting criteria based on U cos φ characteristic,the measured impedance locus and the apparent impedance angle can hardly adapt to the multi-frequency oscillation scenario.It is advised that the two splitting criteria,apparent impedance angle and phase angle difference cooperate with each other to improve the correctness of out-of-step separation equipment.

关键词

热稳定安全域/多维空间/多约束/分段线性近似

Key words

out-of-step oscillation/oscillation center/asynchronous operation/power system stability

引用本文复制引用

夏成军,陈翠琼,涂亮,陈亦平,门锟..多频振荡下失步解列判据的适用性分析[J].电力系统自动化,2016,(4):26-31,6.

基金项目

国家高技术研究发展计划(863计划)资助项目(2012AA050209)。This work is supported by National High Technology Research and Development Program of China (863 Program)(No.2012AA050209) (863计划)

电力系统自动化

OA北大核心CSCDCSTPCD

1000-1026

访问量0
|
下载量0
段落导航相关论文