| 注册
首页|期刊导航|电力系统自动化|动态无功补偿装置提高多馈入直流恢复的布点方法

动态无功补偿装置提高多馈入直流恢复的布点方法

张红丽 刘福锁 李威

电力系统自动化Issue(5):133-138,6.
电力系统自动化Issue(5):133-138,6.DOI:10.7500/AEPS20150518001

动态无功补偿装置提高多馈入直流恢复的布点方法

Site Selection for Dynamic Reactive Power Compensation and Improvement of Recovery from Commutation Failures in Multi-infeed HVDC System

张红丽 1刘福锁 2李威1

作者信息

  • 1. 国电南瑞科技股份有限公司,江苏省南京市 211106
  • 2. 智能电网保护与运行控制国家重点实验室,江苏省南京市 211106
  • 折叠

摘要

Abstract

In order to choose the suitable point of dynamic reactive power compensation equipments and improve the ability of recovering from DC commutation failures,a method of installing dynamic reactive power compensation equipments is adopted with the price of stability for commutation failures taken into account.The internal relation between multi-infeed interaction factor and commutation failures are analysed so that the effects between DC can be judged in advance.The boundary of dynamic reactive power zone is determined,and the sensitivity of commutation failures is defined.The proportion of multi-infeed DC influence is considered to quickly determine the best compensation position.Plenty of grid simulation results show that for the same capacity of dynamic reactive power compensation equipments, the recommended scheme can effectively reduce commutation failures taking place on several multi-infeed DC lines due to AC faults.

关键词

多馈入高压直流系统/动态无功补偿/换相失败/多馈入交互作用因子

Key words

multi-infeed HVDC system/dynamic reactive power compensation/commutation failure/multi-infeed interaction factor(MIIF)

引用本文复制引用

张红丽,刘福锁,李威..动态无功补偿装置提高多馈入直流恢复的布点方法[J].电力系统自动化,2016,(5):133-138,6.

电力系统自动化

OA北大核心CSCDCSTPCD

1000-1026

访问量0
|
下载量0
段落导航相关论文