| 注册
首页|期刊导航|长江科学院院报|二滩水电站监控系统改造几起典型故障分析

二滩水电站监控系统改造几起典型故障分析

席光庆 周瑜 李阳阳 武法磊 周琪 周胜伟 简振远 宋永恒

长江科学院院报2016,Vol.33Issue(2):123-127,5.
长江科学院院报2016,Vol.33Issue(2):123-127,5.DOI:10.11988/ckyyb.20140867

二滩水电站监控系统改造几起典型故障分析

Typical Faults in the Technical Reform of Monitoring and Control System for Ertan Hydropower Plant

席光庆 1周瑜 1李阳阳 1武法磊 1周琪 1周胜伟 1简振远 1宋永恒1

作者信息

  • 1. 雅砻江流域水电开发有限公司,成都 610051
  • 折叠

摘要

Abstract

In the process of technical renovation for the monitoring and control system, there are four typical faults:false alarm signals, abnormal data communication in dispatch communication system, slow data refreshing of the 101 communication protocol and AGC/AVC workstation crash. Through analysis, we found that these faults are caused by circuit electromagnetic interference, software bugs, ill⁃considered procedures, outdated firmware version and unreasonable allocation in calculation procedures, respectively. We can solve all the faults by strengthening cir⁃cuit anti⁃interference ability and filtering signals in the program, removing program bugs , reasonably arranging the start⁃stop time and orders in processing sequence, optimizing process and strategies to reduce the amount of data sent and shorten the queues length, upgrading the firmware version, and optimizing the load distribution of calcula⁃tion program to avoid halt of AGC/AVC workstation system. Results show that the measures are effective.

关键词

二滩水电站/监控系统/调度通信/AGC/AVC/IEC60870-5-104

Key words

Ertan hydropower plant/monitoring and control system/dispatch communication system/AGC/AVC/IEC60870-5-104

分类

信息技术与安全科学

引用本文复制引用

席光庆,周瑜,李阳阳,武法磊,周琪,周胜伟,简振远,宋永恒..二滩水电站监控系统改造几起典型故障分析[J].长江科学院院报,2016,33(2):123-127,5.

长江科学院院报

OA北大核心CSCDCSTPCD

1001-5485

访问量0
|
下载量0
段落导航相关论文