广东电力2016,Vol.29Issue(3):16-19,4.DOI:10.3969/j.issn.1007-290X.2016.03.004
甩负荷识别功能在1000 MW 机组中的应用
Application of Load Shedding Recognition in 1 000 MW Unit
曾海波 1姚峰 1肖波 1韩高岩2
作者信息
- 1. 国电汉川发电有限公司,湖北 汉川 431614
- 2. 浙江省电力试验研究院,浙江 杭州 310014
- 折叠
摘要
Abstract
In view of the situation that some newly constructed large units cancel over-speed control (OPC)function and me-chanical emergency trip devices,this paper analyzes logical judgement of load shedding recognition of Siemens SPPA-T3000 system and operation mode of its digital electric hydraulic (DEH)control system after its action by combining an event of once instantaneous power grid fault of some 1 000 MW ultra-supercritical unit which caused the unit over-speed. It points out after making quantitative analysis on changes of parameters in quick closing function of the governing valve that load shed-ding is not the only reason for quick closing of the governing valve,and it also concludes possible reasons for closing of the governing valve.关键词
甩负荷识别/数字电液控制系统/快关Key words
load shedding recognition/digital electric hydraulic (DEH)control system/quick closing分类
能源与动力引用本文复制引用