电力系统自动化2016,Vol.40Issue(7):61-67,148,8.DOI:10.7500/AEPS20150612005
提升无源工业负荷故障穿越能力的VSC-HVDC控制策略
Enhanced Fault Ride-through Method for VSC-HVDC Supply of Passive Industrial Installations
卞志鹏 1徐政 1宣羿1
作者信息
- 1. 浙江大学电气工程学院,浙江省杭州市 310027
- 折叠
摘要
Abstract
Since industrial installations are much more sensitive to voltage drops than frequency deviations,it is essential to guarantee the stability of voltage during severe faults.First,the main factor that affects the AC voltage in the passive system is analyzed.According to the analytical results,the control strategy is proposed to increase the AC voltage in transient conditions.The strategy consists of two parts,i.e.,a modified current limit tactic and a frequency hysteresis control.The simulation tests uring metallic single-phase and three-phase faults are done via PSCAD/EMTDC to verify the validity of the control methods.关键词
无源工业负荷/频率滞回控制/限幅策略/电压跌落/电压源换流器型直流输电(VSC-HVDC)Key words
passive industrial installations/frequency hysteresis control/limit strategy/voltage sag/voltage source converter based high voltage direct current(VSC-HVDC)引用本文复制引用
卞志鹏,徐政,宣羿..提升无源工业负荷故障穿越能力的VSC-HVDC控制策略[J].电力系统自动化,2016,40(7):61-67,148,8.