邓朴 刘晓波 皮显松 王丰元 刘凯

电力系统保护与控制2016,Vol.44Issue(10):71-78,8.
电力系统保护与控制2016,Vol.44Issue(10):71-78,8.DOI:10.7667/PSPC150887

电容器串联电抗消除谐振的最大值最小优化

Minimax optimization of reactance connected in series on capacitor to eliminate resonance

邓朴 1刘晓波 2皮显松 1王丰元 1刘凯3

作者信息

  • 1. 贵州电网公司电网规划研究中心,贵州 贵阳 550002
  • 2. 贵州大学,贵州 贵阳 550025
  • 3. 都匀供电公司,贵州 都匀 558000
  • 折叠

摘要

Abstract

For the reasonable series reactance rate in capacitor of substations, the full parametric harmonic circuit and model for 220 kV and 110 kV substations are established, which consists of short impedance, transformer, capacitor, load, and harmonic source, and the resonance objective function that reflect the degree of resonance such as harmonic voltage amplification factor on load bus, etc. is given. With minimax optimization, the maximum values of objective function in all the power grid parameter space are minimized by changing reactance rate, and the technical and economic characteristics of the reactance rate of the capacitor are analyzed. The calculation results show that resonance is eliminated with best effect and generality by the rate 12%; resonance is eliminated with second effect by rate 4.2% ~ 4.5%, but the rate 4.2% ~ 4.5% one has better technical and economic value and is suitable for most of 220 kV and 110 kV substation.

关键词

谐波/谐振/电容器/谐波放大/电抗率/谐波阻抗/最大值最小优化

Key words

harmonic/resonance/capacitor/harmonic amplification/reactance ratio/harmonic impedance/minimax optimization

引用本文复制引用

邓朴,刘晓波,皮显松,王丰元,刘凯..电容器串联电抗消除谐振的最大值最小优化[J].电力系统保护与控制,2016,44(10):71-78,8.