| 注册
首页|期刊导航|电力系统保护与控制|一种新模式常规采样 GOOSE 跳闸变压器保护的设计及应用

一种新模式常规采样 GOOSE 跳闸变压器保护的设计及应用

陈继瑞 刘立功 李旭 邓茂军 张营伟 李宝伟

电力系统保护与控制2016,Vol.44Issue(10):98-103,6.
电力系统保护与控制2016,Vol.44Issue(10):98-103,6.DOI:10.7667/PSPC151150

一种新模式常规采样 GOOSE 跳闸变压器保护的设计及应用

Design and application of a new model conventional sampling and GOOSE tripping transformer protection

陈继瑞 1刘立功 1李旭 1邓茂军 1张营伟 1李宝伟1

作者信息

  • 1. 许继集团有限公司,河南 许昌 461000
  • 折叠

摘要

Abstract

To solve sampling-data anomalies of smart substations caused by the complex digital sampling circuit links, this paper puts forward a new model transformer protection design method based on regular sampling and GOOSE trip. NPI plugs is used to achieve new sampling circuit and GOOSE information transmission of analog double AD-directly sampling, and coupled with double AD real-time sampling data validation criterion based on sliding data windows, the effectiveness of sampling data is checked. In addition, for UHV transformer inrush current characteristics, it proposes a comprehensive inrush current identification criterion of differential current harmonics blocking each other and discontinuity points opening, the simulation results show that comprehensive inrush current identification criterion can be applied to the new model transformer protection.

关键词

变压器/智能变电站/滑动数据窗/常规采样/励磁涌流/双AD

Key words

transformer/smart substation/sliding data window/conventional sampling/inrush current/double AD

引用本文复制引用

陈继瑞,刘立功,李旭,邓茂军,张营伟,李宝伟..一种新模式常规采样 GOOSE 跳闸变压器保护的设计及应用[J].电力系统保护与控制,2016,44(10):98-103,6.

电力系统保护与控制

OA北大核心CSCDCSTPCD

1674-3415

访问量0
|
下载量0
段落导航相关论文