| 注册
首页|期刊导航|电力系统自动化|特高压混合无功补偿线路接地故障开断特性

特高压混合无功补偿线路接地故障开断特性

韩明明 李清泉 刘洪顺 李斌 吕婷婷 王者

电力系统自动化2016,Vol.40Issue(12):158-164,7.
电力系统自动化2016,Vol.40Issue(12):158-164,7.DOI:10.7500/AEPS20151022005

特高压混合无功补偿线路接地故障开断特性

Interrupting Characteristics of Ground Fault on UHV Transmission Line with Hybrid Reactive Compensation

韩明明 1李清泉 2刘洪顺 1李斌 2吕婷婷 1王者2

作者信息

  • 1. 山东大学电气工程学院,山东省济南市 250061
  • 2. 山东省特高压输变电技术与装备重点实验室 山东大学,山东省济南市 250061
  • 折叠

摘要

Abstract

When ground fault occurs on ultra-high voltage (UHV) transmission line with hybrid reactive power compensation using stepped controlled reactor and series compensation equipment,the transient recovery voltage(TRV)at both ends of the circuit breaker will show different characteristics by the related factors of hybrid reactive power compensation.Based on a simplified model of the UHV grounding fault network,the calculation expressions of the rate of rise of recovery voltage (RRRV) and the peak value of TRV are derived by theoretical analysis in the case of not shortened capacitor banks of series compensation when the circuit breaker opens.The waveform characteristics of TRV and the effect of hybrid reactive power compensation degree on breaking characteristics of the circuit breaker is analyzed by simulation in the case of shortening of series compensation at different times when the circuit breaker opens.The results show that RRRV and TRV peak decrease with an increase in the fault distance when the capacitor group of series compensation is not shortened and the length of the overhead line is fixed.When the length of overhead line is increased over 1 100 km,resonance will occur in UHV power grid when ground fault occurs.If the overhead line is shorter than 1 100 km,RRRV and TRV peak will increase with the length of the overhead lines getting longer.The more difficult it is to break the circuit breaker,the bigger the voltage value of power will be when the series capacitor group is shortened,while the increase in the compensation degree of series compensation and stepped controlled reactor is more conducive to the circuit breaker opening.

关键词

混合无功补偿/串补装置/暂态恢复电压/瞬态恢复电压上升率/补偿度

Key words

hybrid reactive power compensation/series compensation device/transient recovery voltage(TRV)/rate of rise of recovery voltage (RRRV)/compensation degree

引用本文复制引用

韩明明,李清泉,刘洪顺,李斌,吕婷婷,王者..特高压混合无功补偿线路接地故障开断特性[J].电力系统自动化,2016,40(12):158-164,7.

基金项目

国家自然科学基金资助项目(51507095)。@@@@This work is supported by National Natural Science Foundation of China(No.51507095) (51507095)

电力系统自动化

OA北大核心CSCDCSTPCD

1000-1026

访问量0
|
下载量0
段落导航相关论文