夏溢 邰能灵 范春菊 于仲安

电力系统保护与控制Issue(18):9-16,8.
电力系统保护与控制Issue(18):9-16,8.

参数不对称同塔四回输电线的零序四分量法及故障分析

Four zero-sequence component method of asymmetry-parameter four-parallel lines on the same tower and its fault analysis

夏溢 1邰能灵 1范春菊 1于仲安2

作者信息

  • 1. 上海交通大学电子信息与电气工程学院,上海,200240
  • 2. 江西理工大学电气工程与自动化学院,江西 赣州,341000
  • 折叠

摘要

Abstract

Many four-parallel lines on the same tower show the asymmetry of parameters. A new phase-mode transform introduced is introduced to totally decouple the asymmetric matrix and improve the accuracy of fault analysis of four-parallel lines. Referring decoupling method of existing phase-mode transformation, four zero-sequence component method (FZCM) is proposed. Keeping positive and negative sequence components unchanged, this method introduces a same-direction component and three circulation components with correction factors to decouple the matrix. FZCM can be applied to fault analysis of asymmetry-parameter four-parallel lines under same voltage grade or different voltage grades. Fault sequence network can be figured out by the sequence component definition and fault boundary condition. Simulation results prove the validity of four zero-sequence component method for fault analysis. This work is supported by National Natural Science Foundation of China (No. 51177066).

关键词

同塔四回线/参数不对称/零序四分量法/解耦/故障分析

Key words

four-parallel lines on the same tower/parameters unbalance/four zero-sequence component method/decoupling/fault analysis

分类

信息技术与安全科学

引用本文复制引用

夏溢,邰能灵,范春菊,于仲安..参数不对称同塔四回输电线的零序四分量法及故障分析[J].电力系统保护与控制,2013,(18):9-16,8.

基金项目

国家自然科学基金资助项目 ()

电力系统保护与控制

OA北大核心CSCDCSTPCD

1674-3415

访问量0
|
下载量0
段落导航相关论文