内蒙古电力技术2016,Vol.34Issue(3):31-34,4.DOI:10.3969/j.issn.1008-6218.2016.03.010
6 kV厂用母线电压互感器二次侧断路器跳闸原因分析
Tripping Cause Analysis of Secondary Side Circuit Breaker on 6 kV Factory Busbar Voltage Transformer
杨秀林1
作者信息
- 1. 神华亿利能源有限责任公司,内蒙古 鄂尔多斯 014300
- 折叠
摘要
Abstract
Shenhua Yili Energy Co., Ltd. 6 kV factory busbar voltage transformer neutral point breakdown fuse (JBO) on the low voltage side under normal operating voltage was broke down, lead to 6 kV factory busbar voltage transformer secondary side circuit breaker short circuit trip. Through analysis, because the system ferroresonance overvoltage caused JBO was broken down, pointed out that the currently used JBO under the rated working voltage was broken down might cause a series of safety problems. Based on the system operation mode, put forward with the modified product, namely the electronic breakdown fuse (NYD-JBO) alternative JBO suggestion.关键词
6 kV厂用母线/电压互感器/断路器/击穿保险器/击穿/电子式击穿保险器Key words
6 kV factory busbar/voltage transformer/circuit breaker/broken down insurance/breakdown/electronic breakdown insurance分类
信息技术与安全科学引用本文复制引用
杨秀林..6 kV厂用母线电压互感器二次侧断路器跳闸原因分析[J].内蒙古电力技术,2016,34(3):31-34,4.