水电机组调速器双机故障切换原因分析及处理
Analysis and Treatment of Dual System Fault Switch for Governor of Hydropower Unit
吴博 1赵远新 1谢经鹏 1栾少帅1
作者信息
- 1. 黄河万家寨水利枢纽有限公司龙口水电站,内蒙古 鄂尔多斯 017000
- 折叠
摘要
Abstract
Y.R. Wanjiazhai Water Multi-Purpose Dam Project Co., Ltd. Longkou Hydropower Station turbine governor system frequently occurded abnormal phenomena of dual channel automatically switch control from March to May 2015, according to the governor of dual computer switching logic programs, troubleshoot the cause of the malfunction, through control channel element feedback signal waveforms analysis, determined the failure cause of the driving plate adjusting zero amplitude modulation part operational amplifier chip performance degradation caused by the governor of double frequent automatic switching. To solve the phenomenon of dual machine fault switching, the governor was adopted to modify the program, add filter function, replace the driver board chips, reduce the interference level of the feedback signals, solved the fault completely.关键词
水电站/调速器/故障切换/导叶传感器/反馈信号/录波/可编程计算机控制器Key words
hydropower station/governor/fault switch/guide vane sensor/feedback signal/wave recorder/programmable computer controller(PCC)分类