摘要
Abstract
According to misoperation of injection stator eartching fault protection in the process of electric braking in Guang-zhou pumped storage power station,this paper analyzes influence of the third harmonic voltage of stator neutral point on al-gorithm for injection stator earthing fault protection under the working condition of generator electric braking. It also stud-ies action conditions causing protection misoperation. Meanwhile,it presents solutions to optimize protection logic so as to prevent protection misoperation and improve protection reliability.关键词
发电机/定子接地保护/三次谐波电压/注入式/保护误动Key words
generator/stator earthing fault protection/third harmonic voltage/injection/protection misopeartion分类