流体机械2016,Vol.44Issue(7):63-69,7.DOI:10.3969/j.issn.1005-0329.2016.07.014
组合式空调箱中盘管热回收的性能分析
Performance Analysis on the Coil -heat Recovery in Air Handle Unit
摘要
Abstract
The performance of coil -heat recovery used by air handle unit is variable with not only condition parameters,but al-so structure parameters.Lumped parameter model is designed,the calculated results of the model were verified by the experimental data:the mean relative deviations are lower than 5.3% and the maximal relative deviations are lower than 7%.Based on this model,the effects of flow circuits,fin pitch,number of tube rows alone the airflow direction,air volume,and water speed on the coil heat recovery performance are investigated,which provide the basis for the selection of coil heat recovery in air handle unit.关键词
组合式空调箱/盘管热回收/热回收效率/性能仿真Key words
air handle unit/coil heat recovery/heat recovery efficiency/performance simulation分类
机械制造引用本文复制引用
王磊,谷波,冯梦怡..组合式空调箱中盘管热回收的性能分析[J].流体机械,2016,44(7):63-69,7.