南方电网技术2016,Vol.10Issue(7):13-16,23,5.DOI:10.13648/j.cnki.issn1674-0629.2016.07.003
异步联网后云南电网的稳定特性与控制措施
Stability Characteristics and Control Measures of Yunnan Power Grid After Asynchronous Interconnection
杜斌 1张丹 2张军民 3徐敏 1柳勇军 1涂亮 1付超 1吴小珊1
作者信息
- 1. 南方电网科学研究院,广州510080
- 2. 云南电力调度控制中心,昆明650041
- 3. 国网苏州供电公司,浙江苏州215000
- 折叠
摘要
Abstract
Yunnan Power Grid is planned to operate asynchronously with the main grid of China Southern Power Grid (CSG). When the time comes,the anti-interference ability of Yunnan Power Grid will be poor since it has a small system capacity and operates inde-pendently. There might be power angel problems and high frequency stability problems after DC system is blocked,and low frequency problems after large generators are tripped. This paper analyzes the stability characteristics of Yunnan Power Grid after asynchronous interconnection with CSG,also analyzes and assesses the effects of five stability control measures groups through simulation and com-parison,finally proposes control measures such as generator tripping combined with FLC for high frequency problems,and decreasing DC power through FLC and shedding load for low frequency problems.关键词
异步联网/功角稳定/频率稳定/频率限制Key words
asynchronously interconnected/angular stability/frequency stability/frequency limit分类
信息技术与安全科学引用本文复制引用