南方电网技术2016,Vol.10Issue(7):29-34,6.DOI:10.13648/j.cnki.issn1674-0629.2016.07.006
异步联网方式下云南电网超低频振荡的机理分析与仿真
Mechanism Analysis and Simulation on Ultra-Low Frequency Oscillation of Yunnan Power Grid in Asynchronous Interconnection Mode
刘春晓 1张俊峰 2陈亦平 1张建新 1徐敏 3王官宏4
作者信息
- 1. 中国南方电网电力调度控制中心,广州510623
- 2. 广东电网有限责任公司电力科学研究院,广州510080
- 3. 南方电网科学研究院,广州510080
- 4. 中国电力科学研究院,北京100192
- 折叠
摘要
Abstract
The asynchronous interconnection mode between Yunnan Power Grid and China Southern Power Grid is planned to be put into practice in 2016. However,during the practical experiment of raising DC power in asynchronous mode,the frequency of Yunnan Power Grid oscillates in ultra-low frequency for a long period. In this paper,through detailed analysis of the experiment data,the gov-ernor systems of hydropower units are found to be the direct reason of the oscillation,and the mechanism of governor systems offering negative damping during the oscillation is analysed. Furthermore,off-line data simulation is carried out to reproduce the process of this practical experiment,the results prove the correctness of the theory,finally some preliminary recommendations are proposed for further work.关键词
异步联网/超低频振荡/调速系统/仿真Key words
asynchronous interconnection/ultra-low frequency oscillation/governor system/simulation分类
信息技术与安全科学引用本文复制引用
刘春晓,张俊峰,陈亦平,张建新,徐敏,王官宏..异步联网方式下云南电网超低频振荡的机理分析与仿真[J].南方电网技术,2016,10(7):29-34,6.