南方电网技术2016,Vol.10Issue(7):35-39,5.DOI:10.13648/j.cnki.issn1674-0629.2016.07.007
异步联网方式下云南电网超低频振荡的抑制措施与试验
Countermeasures and Experiments on Ultra-Low Frequency Oscillation of Yunnan Power Grid in Asynchronous Interconnection Mode
张建新 1刘春晓 1陈亦平 1张勇 1黄河 1付超 2李鹏2
作者信息
- 1. 中国南方电网电力调度控制中心,广州510623
- 2. 南方电网科学研究院,广州510080
- 折叠
摘要
Abstract
During the practical asynchronous interconnection experiment,Yunnan Power Grid experienced an ultra-low frequency os-cillation for a long period,which threatened the security and stability of China Southern Power Grid(CSG). In this paper,the effects of different hydro governor parameters and HVDC frequency limitation control (FLC)on the frequency stability are analyzed in a sin-gle-generator system and the BPA simulation system. From a large amount of simulation,the measures of optimally adjusting the dead zones and PI parameters of hydro governors are proposed,and the characteristics of different measures are compared. The proposed measures can effectively solve the ultra-low frequency oscillation problem in asynchronous interconnection mode of Yunnan Power Grid,which has been verified by the large and small disturbance experiments on the actual power grid.关键词
异步联网/超低频振荡/抑制措施/水轮机调速器/一次调频/试验验证Key words
asynchronous interconnection/ultra-low frequency oscillation/countermeasures/hydro governors/primary frequency control/experimental verification分类
信息技术与安全科学引用本文复制引用
张建新,刘春晓,陈亦平,张勇,黄河,付超,李鹏..异步联网方式下云南电网超低频振荡的抑制措施与试验[J].南方电网技术,2016,10(7):35-39,5.