首页|期刊导航|电测与仪表|智能变电站采样值同步异常导致跨间隔计量系统故障分析

智能变电站采样值同步异常导致跨间隔计量系统故障分析

李福超 罗睿希 刘鹍 王睿晗 何培东

电测与仪表2016,Vol.53Issue(z1):101-105,5.
电测与仪表2016,Vol.53Issue(z1):101-105,5.

智能变电站采样值同步异常导致跨间隔计量系统故障分析

Fault analysis of multi-bay metering system caused by sampled values synchronous anomaly in smart substation

李福超 1罗睿希 1刘鹍 1王睿晗 1何培东1

作者信息

  • 1. 国网四川省电力公司计量中心,成都610045
  • 折叠

摘要

Abstract

In the design of smart substation, such as internal bridge connection, 3/2 connection and bus PT cascade, digi-tal metering system need to be multi-bay metering. The synchronization of sampled values is the key factor to affect the overall accuracy of digital metering system. This paper introduced the principle of multi-bay metering by digital meter-ing devices in 110 kV Smart Substation which using internal bridge connection design. The inaccurate metering situa-tion in the operation of an 110 kV smart substation is analyzed which caused by the synchronous anomaly of sampled values. And a scheme to improve the reliability of the multi-bay metering in smart substations was proposed.

关键词

智能变电站/数字化计量/电子式互感器/内桥接线/跨间隔计量/采样值/同步

Key words

smart substation/digital metering/electronic transformer/internal bridge connection/multi-bay metering/sampled value/synchronization