| 注册
首页|期刊导航|电网技术|特高压直流输电工程直流分压器动态特性及其引起的误闭锁机理研究

特高压直流输电工程直流分压器动态特性及其引起的误闭锁机理研究

滕予非 汤涌 汪晓华 陈刚 刘耀 张宏图

电网技术2016,Vol.40Issue(9):2646-2653,8.
电网技术2016,Vol.40Issue(9):2646-2653,8.DOI:10.13335/j.1000-3673.pst.2016.09.010

特高压直流输电工程直流分压器动态特性及其引起的误闭锁机理研究

Mechanism Analysis of Error Block Caused by Dynamic Characteristics of DC Voltage Divider in UHVDC

滕予非 1汤涌 2汪晓华 1陈刚 1刘耀 2张宏图3

作者信息

  • 1. 国网四川省电力公司电力科学研究院,四川省成都市 610072
  • 2. 中国电力科学研究院,北京市海淀区 100192
  • 3. 国网四川省电力公司,四川省成都市 610072
  • 折叠

摘要

Abstract

In order to conduct mechanism analysis of error block caused by dynamic characteristics of DC voltage divider (DCVD) in UHVDC, transient breakdown process in DCVD secondary side is theoretically derived by means of transfer function derivation in the paper firstly. Theoretical results show that even primary side DC voltage remains unchanged after breakdown in DCVD secondary side, voltage measurement results also experience a transient process of hundred milliseconds before it returns to normal levels. Secondly, an accident of HVDC block caused by DCVD is analyzed. Response characteristics of control and protection system are studied, and HVDC error block mechanism is proposed. Thirdly, correctness of theoretical analysis is verified with PSCAD/EMTDC simulation, and some countermeasures for avoiding the accidents are proposed. Finally, analysis shows that there is no risk of HVDC error block on condition of breakdown in secondary side of inverter DCVD.

关键词

高压直流/直流分压器/控制保护系统/VDCOL/欠压保护

Key words

HVDC/DC voltage divider/control and protection system/VDCOL/under-voltage protection

分类

信息技术与安全科学

引用本文复制引用

滕予非,汤涌,汪晓华,陈刚,刘耀,张宏图..特高压直流输电工程直流分压器动态特性及其引起的误闭锁机理研究[J].电网技术,2016,40(9):2646-2653,8.

基金项目

国家电网公司科技项目(特高压直流控制封装环节仿真建模处理技术研究与应用)。 Project Supported by State Grid Science & Technology Project (特高压直流控制封装环节仿真建模处理技术研究与应用)

电网技术

OA北大核心CSCDCSTPCD

1000-3673

访问量0
|
下载量0
段落导航相关论文