广东电力2016,Vol.29Issue(9):78-83,6.DOI:10.3969/j.issn.1007-290X.2016.09.016
玻璃钢保护壳对电缆接头热场影响的实验分析
Experiment Analysis on Influence of Glass Fiber Reinforced Plastic Protection Shell on Thermal Field of Cable Joint
摘要
Abstract
There exists temperature gradient along axial direction of the conductor in high voltage (HV)cable joint under the condition of stable loading current,and whether installing glass fiber reinforced plastic (FRP)protection shell may affect axial temperature distribution of the joint. In order to analyze influence of glass FRP protection shell on axial temperature distribution of the intermediate joint of cable,a set of experiment system for large current temperature rise for HV cable is designed and experiments on 630 mm2 cable joint respectively with glass FRP protection shell and without glass FRP protec-tion shell under the condition of stable loading current are finished. Experimental results indicate that the glass FRP protec-tion shell will make axial and radial temperature of the cable joint both increase and influence scope of the joint on the con-ductor also increases.关键词
电缆接头/玻璃钢保护壳/大电流实验系统/轴向温度/径向温度Key words
cable joint/glass fiber reinforced plastic protection shell/large current experimental system/axial temperature/radial temperature分类
信息技术与安全科学引用本文复制引用
徐研,王鹏宇,刘毅刚,郭珊珊,王振华,刘刚..玻璃钢保护壳对电缆接头热场影响的实验分析[J].广东电力,2016,29(9):78-83,6.基金项目
国家高技术研究发展计划(863计划)项目(2015AA050201) (863计划)