Aiming at two cases of main transformer trip fault continuously happened in a 220 kV substation, according to failure informations and relevant test results, finds out the causes of main transformer trip, puts forward the measures such as to develop partial discharge detection before the commission of resin-casting type current transformer, and to generalize the grounding transfer technology in non- effectively neutral grounded system. The application result shows that the improving measure can effectively prevent main transformer trip fault happening due to main insulation breakdown of resin-casting type current transformer.

关键词

主变压器/跳闸故障/浇注式电流互感器/局部放电/绝缘击穿/中性点非有效接地系统/接地转移技术

Key words

main transformer/trip fault/resin-casting type current transformer/partial discharge/insulation breakdown/non-effectively neutral grounded system/grounding transfer technology