电测与仪表2016,Vol.53Issue(16):50-55,6.
永磁直驱风力发电系统的低电压穿越控制策略
Low voltage ride through control strategy for permanent magnet direct-drive wind power generation system
周士琼 1王倩 1陈隆 1倪亚玲 2吕潇1
作者信息
- 1. 西南交通大学 电气工程学院,成都 610031
- 2. 电子科技大学,成都 610054
- 折叠
摘要
Abstract
In view of the problem of low voltage ride through of permanent magnet direct-drive wind power generation system, this paper improves the traditional control strategies, and increases power feed forward control in the machine side, according to the power difference of between the motor and the grid side to adjust motor-side active current quickly to control the torque of the generator, which achieves active power control of the generator.Grid-side convert-er tracks the grid voltage, outputs a constant reactive power according to the dropped level of the grid voltage to sup-port grid voltage recovery.The simulation showed that, the improved control strategy can stabilize the DC bus voltage quickly, which can achieve low-voltage ride through operation of wind turbines.关键词
永磁直驱风电机组/功率前馈控制/无功支撑/低电压穿越Key words
permanent magnet direct drive wind turbines/power feedforward control/reactive power support/low -voltage ride through分类
信息技术与安全科学引用本文复制引用
周士琼,王倩,陈隆,倪亚玲,吕潇..永磁直驱风力发电系统的低电压穿越控制策略[J].电测与仪表,2016,53(16):50-55,6.