湖北电力2016,Vol.40Issue(4):32-35,4.DOI:10.19308/j.hep.2016.04.008
一起调试期间500 kV SF6断路器灭弧室瓷套爆炸原因的分析
Analysis of an Explosion of the Porcelain Sleeve of 500 kV SF6 Circuit Breaker during the Commissioning Period
于建龙1
作者信息
- 1. 国网福建省电力有限公司,福建 福州 350003
- 折叠
摘要
Abstract
Acording to an explosion accident of the porcelain sleeve of 500 kV SF6 Circuit Break⁃er during the Commissioning Period,based on the inspection of explosion site and a series of verifi⁃cation test of porcelain sleeve, and a series of validation experiments on the adaptability of the por⁃celain bushing under high and low temperature conditions, crack in the firing process, internal pressure level, mechanical loading capacity, the compact structure and the uniformity of porcelain are carried out. Finally the reason of the explosion of the porcelain sleeve proves to be the crack of porcelain sleeve produced in manufacturing or transportation process. Two measures for avord⁃ing to produce the crack of the porcelain sleeve are proposed in this paper.关键词
高压断路器/灭弧室/瓷套/爆炸Key words
high-voltage circuit breaker/interrupter/porcelain sleeve/explosion分类
信息技术与安全科学引用本文复制引用
于建龙..一起调试期间500 kV SF6断路器灭弧室瓷套爆炸原因的分析[J].湖北电力,2016,40(4):32-35,4.