制冷学报2016,Vol.37Issue(5):57-62,6.DOI:10.3969/j.issn.0253-4339.2016.05.057
基于中间补气压缩机的地暖系统制热性能实验研究
Experimental Investigation on Heating Performance of Under-floor Heating System based on Vapor-injection Compressor
摘要
Abstract
The scroll compression with vapor injection is applied to under⁃floor heating system to solve the problems of poor heating per⁃formance and instability operation under the condition of low ambient temperature in this paper. The compressor discharge temperature, heating performance, power consumption and COP( Coefficient of Performance) are researched and compared with the heating system with⁃out vapor injection. The results show that under the ambient temperatures between -20℃ and 7℃, the under⁃floor heating system based on vapor⁃injection compressor has a higher heating capacity and COP compared with the normal heating pump , and the heating capacity is increased by 26. 2%, and the COP is increased by 8. 7% on average, and power consumption is only increased by 16% on average;and when the ambient temperature is -20 ℃,the discharge temperature is decreased 12 ℃. The experimental results demonstrate that the un⁃der⁃floor heating system based on vapor⁃injection compressor can better satisfy the demands of low ambient temperature with low energy consumption.关键词
中间补气/涡旋式压缩机/地暖系统/制热性能Key words
vapor injection/scroll compression/under-floor heating system/heating capacity分类
通用工业技术引用本文复制引用
费继友,王英邗,张文强,李花,谢金路,陈东东,梁晟铭..基于中间补气压缩机的地暖系统制热性能实验研究[J].制冷学报,2016,37(5):57-62,6.基金项目
国家自然科学基金(51376028)和国家科技支撑计划(2015BAF20B02)资助项目。(The project was supported by the National Natural Science Foundation of China ( No.51376028) and National Key Technology R&D Program of China(No.2015BAF20B02).) ()