制冷学报2016,Vol.37Issue(5):63-69,7.DOI:10.3969/j.issn.0253-4339.2016.05.063
太阳能驱动的除湿空调系统冬季工况下的实验研究
Experimental Investigation on Solar Powered Desiccant Air-conditioning System in Winter
摘要
Abstract
The objective is to validate the humidifying performance of a solid desiccant coated heat exchanger ( DCHE) cooling system in winter. The experimental setup is designed and built to test the humidifying performance. In this system, the heating water required in re⁃generation process is coming from the solar collector system. The saturated desiccant is regenerated by the heating water, at the same time the regeneration air is humidified and heated. Under the condition of the temperature of the heating water is 42. 0 ℃, the temperature of the air increases from 12. 1 ℃ to 31. 2 ℃. The average moisture addition Dave is 3. 4 g/kg. The thermal coefficient of performance COPth is about 2. 0.关键词
干燥剂/再生/除湿换热器/冬季工况Key words
desiccant/regeneration/desiccant coated heat exchanger/winter conditions分类
建筑与水利引用本文复制引用
王惠惠,葛天舒,章学来,赵耀..太阳能驱动的除湿空调系统冬季工况下的实验研究[J].制冷学报,2016,37(5):63-69,7.基金项目
国家自然科学基金(51336004)资助项目。( The project was supported by the National Natural Science Foundation of China ( No.51336004).) ()