基于特高频法的1100 kV GIS局部放电缺陷定位研究
Application of UHF Method on Partial Discharge Detection in GIS
杨勇 1王泓学 2吴胥阳 3王绍安 1张静4
作者信息
- 1. 国网浙江省电力公司电力科学研究院,杭州 310014
- 2. 国网浙江省电力公司宁波供电公司,浙江 宁波 315000
- 3. 国网浙江省电力公司金华供电公司,浙江 金华 321017
- 4. 国网浙江省电力公司培训中心,杭州 310018
- 折叠
摘要
Abstract
According to a live detection of 1 100 kV GIS, this paper describes the principles and technical advantages of UHF-based GIS partial discharge detection method;in addition, it analyzes the spectrogram in-formation of portable PD analyzer to preliminarily judge the defect type. At last, the discharge source is pre cisely located by means of time difference location method. The result of pattern recognition techniques of 1 100 kV GIS partial discharge on-line monitoring system is consistent with the field test, which verifies the ac-curacy of the on-site live detection. Practice shows that UHF partial discharge detection technique can recog-nize partial discharge due to GIS defects, and timely discover and prevent GIS insulation faults to ensure the operation security and stability of GIS.关键词
特高频/GIS/局部放电/带电检测Key words
UHF/GIS/partial discharge/live detection分类