| 注册
首页|期刊导航|低压电器|金中直流输电系统中直流滤波器保护误动分析

金中直流输电系统中直流滤波器保护误动分析

张鹏望

低压电器Issue(22):61-64,4.
低压电器Issue(22):61-64,4.DOI:10.16628/j.cnki.2095-8188.2016.20.013

金中直流输电系统中直流滤波器保护误动分析

Analysis of DC Filter Protection Malfunction in Jinzhong DC Power Transmission System

张鹏望1

作者信息

  • 1. 中国南方电网超高压输电公司 大理局, 云南 大理 671000
  • 折叠

摘要

Abstract

A DC line fault in its bipolar ground mode leads to DC filter protection malfunction in Jin guan convert station.According to the fault waveform, the fault reason was pointed out.The unreasonable design of DC filter protection leads to ratio differential protection of DC filter in non-protection area.Finally, the optimization suggestions were given.

关键词

直流输电/直流滤波器保护/误动/比率差动保护

Key words

DC transmission/DC filter protection/malfunction/ratio differential protection

分类

信息技术与安全科学

引用本文复制引用

张鹏望..金中直流输电系统中直流滤波器保护误动分析[J].低压电器,2016,(22):61-64,4.

低压电器

1001-5531

访问量0
|
下载量0
段落导航相关论文