湖北电力2016,Vol.40Issue(7):13-16,4.DOI:10.19308/j.hep.2016.07.003
35 kV干式并联电抗器家族缺陷分析及改进措施
Analysis and Countermeasures of 35 kV Dry-type Shunt Reactor Familial Defect
孟毅 1李凯宇1
作者信息
- 1. 国网湖北省电力公司电力科学研究院,湖北 武汉 430077
- 折叠
摘要
Abstract
A familial defect of 35 kV dry-type shunt reactors is introduced, and the causes of the defect are analyzed in this paper. It is found that the installation position of the regulating coil has an important influence on the electric field strength nearby. When the regulating coil is installed at the top of the winding, the local maximum electric field strength near the coil is much larger than that at the bottom of the winding. Partial discharge or breakdown of the regulating coil is easy to oc⁃cur under the condition of the reactor switching overvoltage, which may cause the regulating coil to catch fire and burn the reactor. And the problem existing in the regulating coil manufacturing pro⁃cess is also pointed out. The identification of the familiar defect is introduced. The countermea⁃sures are put forward in the product design, manufacture and maintenance aspects.关键词
干式并联电抗器/家族缺陷/匝线圈/操作过电压Key words
dry-type shunt reactor/familiar defect/regulating coil/switching overvoltage分类
信息技术与安全科学引用本文复制引用
孟毅,李凯宇..35 kV干式并联电抗器家族缺陷分析及改进措施[J].湖北电力,2016,40(7):13-16,4.