电测与仪表2017,Vol.54Issue(4):123-128,6.
低压电力线通信导致漏电保护器误跳闸问题探讨
Study on the error tripping problem of leakage protector for low voltage power line carrier communication
王立城 1胡科军 1高飞 1陈静 1王东山1
作者信息
- 1. 北京智芯微电子科技有限公司,北京 100192
- 折叠
摘要
Abstract
Aiming at the error tripping problem of leakage protector in the domestic users of electric energy information acquisition system,this paper discusses the principle of leakage protector and testing conditions of tripping on site,and analyzes the line structure,signal transmission and error tripping of leakage protector in low voltage power line carrier communication residential areas.Then,the theoretic analysis and the experimental evaluation are both conducted from aspects of the impact of power line carrier communication and the anti-interference of leakage protector.The final result can be drawn that the tripping problem may be caused by the anti-interference itself,carrier signal characteristics,device insulation ability and power grid noises,etc.Thus,carrier signal is just one of main reasons leading to tripping problem,while better solution is to improve the design of leakage protector with enhanced anti-interference.关键词
用电信息采集/电力线载波/漏电保护器/误跳闸Key words
electric energy information acquisition/power line carrier/leakage protector/error tripping分类
信息技术与安全科学引用本文复制引用
王立城,胡科军,高飞,陈静,王东山..低压电力线通信导致漏电保护器误跳闸问题探讨[J].电测与仪表,2017,54(4):123-128,6.