电力系统及其自动化学报2017,Vol.29Issue(2):96-100,5.DOI:10.3969/j.issn.1003-8930.2017.02.016
光伏并网下考虑电网安全约束的机组组合
Security Constrained Unit Commitment with Photovoltaic Grid-Connected
黄泽华 1孙义豪 1罗得俊 1杨卓 1胡钋 2汪原浩2
作者信息
- 1. 国网河南省电力公司经济技术研究院,郑州 450000
- 2. 武汉大学电气工程学院,武汉 430072
- 折叠
摘要
Abstract
Based on Benders algorithm,a security constrained unit commitment(SCUC)method with photovoltaic grid-connected is proposed. According to the 2-layer decomposition thought,the SCUC problem is decomposed into the unit commitment without security constraints and the power flow detection in branches considering SCUC,thus the calcula-tion of main problem and sub-problem is formed,which can be solved by mixed integer programming(MIP). Aiming at the detection of main problem,a shifted distribution factor of generation and a penalty variable are introduced to opti-mize the SCUC in terms of security and economical efficiency. The simulation in MATLAB and CPLEX indicates that , with the photovoltaic grid-connected IEEE 14-node system as a test example and as long as the security constraints are satisfied,the overall running cost of the unit commitment decreases compared with that when the commitment is not photovoltaic grid-connected. It is shown that the proposed method can coordinate the security and economical efficiency for the unit commitment.关键词
光伏并网/安全约束机组组合/Benders/混合整数规划/惩罚变量Key words
photovoltaic grid-connected/security constrained unit commitment(SCUC)/Benders/mixed integer pro-gramming(MIP)/penalty variable分类
信息技术与安全科学引用本文复制引用
黄泽华,孙义豪,罗得俊,杨卓,胡钋,汪原浩..光伏并网下考虑电网安全约束的机组组合[J].电力系统及其自动化学报,2017,29(2):96-100,5.