| 注册
首页|期刊导航|高压电器|双断口40.5kV真空容性开断最佳燃弧时间确定试验研究

双断口40.5kV真空容性开断最佳燃弧时间确定试验研究

刘波 田利民 翟小社 陈榆秀 兰贞波

高压电器2017,Vol.53Issue(3):160-166,7.
高压电器2017,Vol.53Issue(3):160-166,7.DOI:10.13296/j.1001-1609.hva.2017.03.025

双断口40.5kV真空容性开断最佳燃弧时间确定试验研究

Experimental Research on Optimal Arcing Time of 40.5 kV Double-break Vacuum Circuit Breaker During Capacitive Interruption Process

刘波 1田利民 2翟小社 3陈榆秀 4兰贞波1

作者信息

  • 1. 南瑞集团(国网电力科学研究院),武汉430074
  • 2. 宝鸡四方华能电气有限公司,西安710049
  • 3. 西安交通大学电气学院,西安710049
  • 4. 麦克奥迪(厦门)电气股份有限公司,福建厦门361101
  • 折叠

摘要

Abstract

To reveal the optimal arcing time of a 40.5 kV double-break vacuum circuit breaker during capacitive interruption when two breaks function non-simultaneously,the voltage distribution characteristics between the two breaks during capacitive interruption were briefly discussed,and the mathematical expression of over-voltage was derived.The values of over-voltage between two breaks in different arcing time were calculated.And a laboratory test was performed on a real 40.5 kV double-break vacuum circuit breaker to verify its re-ignition characteristics during capacitive interruption.As a result,based on the theoretical and test results obtained in this study,the optimal arcing time of the 40.5 kV double-break vacuum circuit breaker with permanent magnet actuator during capacitive interruption is suggested.

关键词

双断口/真空断路器/容性开断/燃弧区间

Key words

double-break/VCB/capacitive interruption/arcing time