高压电器2017,Vol.53Issue(3):254-258,5.DOI:10.13296/j.1001-1609.hva.2017.03.040
KYN28A-12kV/4000A开关柜的结构改进与温度场分析
Structure Modification and Temperature Field Analysis of KYN28A-12 kV/4000 A Switchgear Cabinet
徐立群 1申亮 1倪福生1
作者信息
- 1. 河海大学机电工程学院,江苏常州213022
- 折叠
摘要
Abstract
In view of temperature rise in design of a 12 kV/4 000 A switchgear cabinet,the cabinet's structure of KYN28A-12 kV/4 000 A was modified through limiting heat and improving heat radiation.A simplified 3D model of the structure was established and embedded into the software Ansys to analyze the temperature field in the cabinet.Both simulated and experimental temperature rise values in the modified switchgear cabinet satisfy the standards of GB 3906-2006 and IEC 62271,implying that the structure modification is reasonable.However,the simulated maximum temperature rise point is not consistent with the experimental one,which needs further research.关键词
开关柜/4000 A/结构设计/温度场分析Key words
switchgear cabinet/4000 A/structure design/temperature field analysis引用本文复制引用
徐立群,申亮,倪福生..KYN28A-12kV/4000A开关柜的结构改进与温度场分析[J].高压电器,2017,53(3):254-258,5.