化工学报2016,Vol.67Issue(z2):142-148,7.DOI:10.11949/j.issn.0438-1157.20161412
泵-压缩机复叠式相变冷却系统
Pump-compressor cascade phase-change refrigeration system
摘要
Abstract
The phase-change refrigeration system of cascade pump-compressor is aimed at high heat flux components heat radiation cooling technology.The characteristics of starting and stable operation and the adaptability on high-temperature environment are investigated in this paper.The results show that at the first stage of the mechanical pump starting, because of the flow characteristics of the refrigerant and the inlet suction effect,the pressure increased firstly and then decreased.At the start time of the heat source,less pressure and temperature fluctuations,heat source starts stably.At stable operation stage, not only the flow rate of system increases from 2.2 2 g· s - 1 to 5.5 6 g· s - 1 , but also the dryness of the evaporator’ outlet declines, pressure drop of the evaporator’ outlet increases and the surface temperature of evaporator declines.In the high temperature environment,the refrigeration system can meet the demand of the cooling requirement of heat source,and the fluctuation of pressure and outlet temperature rises.关键词
相变/传热/微通道/启动阶段/稳定运行/高温环境Key words
phase-change/heat-transfer/micro channels/start-up stage/stable operation/high-temperature environment分类
通用工业技术引用本文复制引用
袁俊飞,闫晓娜,张敏慧,王林..泵-压缩机复叠式相变冷却系统[J].化工学报,2016,67(z2):142-148,7.基金项目
国家自然科学基金项目(U1504524)。@@@@supported by the National Natural Science Foundation of China (U1504524) (U1504524)