| 注册
首页|期刊导航|广东电力|110~500kV主变压器油温表运行缺陷的检测与维护策略

110~500kV主变压器油温表运行缺陷的检测与维护策略

覃煜 敖昌民 谢剑翔 许孜博

广东电力2017,Vol.30Issue(1):79-82,92,5.
广东电力2017,Vol.30Issue(1):79-82,92,5.DOI:10.3969/j.issn.1007-290X.2017.01.015

110~500kV主变压器油温表运行缺陷的检测与维护策略

Detection and Maintenance Strategies for Operational Defects of Oil Temperature Gauge of 110~500 kV Main Transformer

覃煜 1敖昌民 1谢剑翔 1许孜博2

作者信息

  • 1. 广州供电局有限公司电力试验研究院,广东广州510410
  • 2. 广州供电局有限公司变电管理三所,广东广州510410
  • 折叠

摘要

Abstract

Oil temperature gauge can monitor temperature of transformer oil in real-time at the moment of transformer running,whether it runs normally or not decides reliability of on-line monitoring on transformer oil temperature and effective or invalid guidance for correct startup of the cooling system of transformer.Thus,it is important to detect operational defects of the transformer oil gauge.Special detection and research on operational defects of the oil temperature gauges of 110 ~500 kV main transformers in Guangzhou region were developed in aspects of voltage class,defect parts,operation time,manufacturers,and so on.Results indicate that there are different operational defects in winding oil temperature gauges and oil face oil temperature gauges,and probability of occurrence of defects are concerned with voltage class,operation time and manufacturers.A few pieces of advices for operational maintenance of the oil temperature gauge are proposed in aspects of planning design,material purchase,engineering construction,maintenance and repair and retired scrap.

关键词

电力变压器/油温表/运行缺陷/电压等级/运行维护

Key words

power transformer/oil temperature gauge/operational defect/voltage class/operational maintenance

分类

信息技术与安全科学

引用本文复制引用

覃煜,敖昌民,谢剑翔,许孜博..110~500kV主变压器油温表运行缺陷的检测与维护策略[J].广东电力,2017,30(1):79-82,92,5.

基金项目

广州供电局有限公司电力试验研究院科技项目(K-GZM2014-027) (K-GZM2014-027)