| 注册
首页|期刊导航|广东电力|500kV曲江变电站2号主变压器低压侧三相对地电压不平衡的原因分析

500kV曲江变电站2号主变压器低压侧三相对地电压不平衡的原因分析

徐兴发 金滇黔

广东电力2017,Vol.30Issue(1):98-102,5.
广东电力2017,Vol.30Issue(1):98-102,5.DOI:10.3969/j.issn.1007-290X.2017.01.019

500kV曲江变电站2号主变压器低压侧三相对地电压不平衡的原因分析

Reason Analysis for Unbalance of Three-phase Voltage to Earth of No.2 Main Transformer Low Voltage Side in Qujiang Substation

徐兴发 1金滇黔1

作者信息

  • 1. 广东电网有限责任公司韶关供电局,广东韶关512026
  • 折叠

摘要

Abstract

Investigation is carried out in allusion to unbalance of three-phase voltage to earth at 35 kV low voltage side of No.2 main transformer in Qujiang substation.By establishing a theoretical analysis model and combining actual structure and measured data of the transformer,this paper calculates and analyzes reasons for causing unbalance of three-phase voltage to earth,and determines that causes are unbalance of equivalent capacitance to earth of 35 kV 2M bus and associated equipment,capacitance between transformer winding and winding ground capacitance.

关键词

主变压器/电压不平衡/电容

Key words

main transformer/voltage unbalance/capacitance

分类

信息技术与安全科学

引用本文复制引用

徐兴发,金滇黔..500kV曲江变电站2号主变压器低压侧三相对地电压不平衡的原因分析[J].广东电力,2017,30(1):98-102,5.

广东电力

OACSTPCD

1007-290X

访问量0
|
下载量0
段落导航相关论文