机械与电子2017,Vol.35Issue(4):35-38,4.
双馈风力发电系统空载并网实验研究
Experimental Research on Idle Load Grid-connection of DFIG Wind Power Generation System
摘要
Abstract
Aiming at the problem that the impulse current caused by grid-connection is large,a grid-connection control strategy based on stator voltage oriented vector is applied to study grid-connection without load of double-fed wind power generation system.Experiment of no-load grid-connection is carried out on a 10 kW simulation platform with Compact RIO real time controller for double-fed wind power generation system, the effects of the difference between the grid voltage and stator voltage in amplitude, phase on the grid-connection impulse current are analyzed.Experimental results show that the value of impulse current shows a process of reducing and then increasing when the speed of rotor increases from low speed to synchronous speed of generator.Change rate of phase difference to impulse current is 10 times larger than change rate of amplitude difference to impulse current averagely.关键词
双馈发电机/空载并网/冲击电流/定子电压定向Key words
doubly-fed induction generator/grid-connection without load/impulse current/stator voltage orientation分类
信息技术与安全科学引用本文复制引用
邓永生,张文斌..双馈风力发电系统空载并网实验研究[J].机械与电子,2017,35(4):35-38,4.基金项目