广东电力2017,Vol.30Issue(3):58-63,6.DOI:10.3969/j.issn.1007-290X.2017.03.011
某变电站10kV并联电容器故障分析及对策
Analysis on 10 kV Parallel Capacitor in One Substation and Relevant Countermeasures
摘要
Abstract
In allusion to the problem of frequent damage of parallel capacitor bank in 10 kV side of one substation, relationship curve between percentage of background harmonic voltage and coefficient of injury of harmonic was drawn on the basis of switching experiment on capacitors and level testing on harmonic in the substation.The direct reason for damage of the capacitor bank was concluded as mismatching of parameters of reactive power compensation capacitor tank and series reactors which consequently caused three times of harmonic enlargement and over-voltage.Simulation experiment verified the conclusion.Combining with field actual situation in this substation, solution of selecting the capacitor bank with 12% reactance rate was proposed.关键词
谐波/无功补偿/电容器/电抗器/电抗率Key words
harmonic/reactive power compensation/capacitor/reactor/reactance rate分类
信息技术与安全科学引用本文复制引用
郭昆丽,田海霞,王建波,王坤..某变电站10kV并联电容器故障分析及对策[J].广东电力,2017,30(3):58-63,6.基金项目
2016年大学生创新创业训练计划项目(2016018),西安工程大学2016年度研究生创新基金项目(CX201618) (2016018)